(0)

AQ M215 Motor Protection Relay

AQ M215-AQ M215 Motor Protection Relay

Sipariş No : AQ M215

AQ M215 offers a modular motor protection and control solution for larger and more important motors requiring both current and voltage based protection functions along with complete measurements of accuracy up to class 0.2S for power and energy. Up to three optional I/O or communication cards are available for more comphrehensive monitoring and control applications. Up to 12 RTD signals can be connected for thermal alarming and tripping.

AQ M215 Motor Protection Relay


Protection Function ANSI     Protection Function ANSI
Three-phase overcurrent protection INST,DT or IDMT - I> ... I>>>> 50/51     Undercurrent / loss of load protection - I< 37
Residual overcurrent protection INST, DT or IDMT - I0> ... I0>>>> 50/51N(S)     Mechanical jam protection - Im> 51m
Directional (sensitive) residual overcurrent protection INST, DT or IDMT - I0> ... I0>>>> 67N(S)     Overvoltage protection DT or IDMT - U>...U>>>> 59
Harmonic overcurrent protection / inrush blocking INST, DT or IDMT - Ixh > ... Ixh >>>> 50/51h/68h     Undervoltage protection DT or IDMT - U 27
Cold load pick-up block – CLPU 68     Residual voltage protection DT or IDMT - U0>...U0>>>> 59N
Current unbalance / broken conductor protection INST, DT or IDMT - I2 (I/I1)>...I2 (I/I1)>>>> 46/46R/46L     Under/over/reverse power protection DT or IDMT - P/Pr...P>>>>/P 32
Low or high-impedance restricted earth-fault / cable end differential protection - I0d> 87N     Frequency protection - f>/f>>>/f<<<< 81U/O
Motor thermal overload protection - T > 49M     Fuse Failure VTS
Motor start-up supervision / locked rotor protection - Ist> 48, 14     CT supervision CTS
Frequent start supervision - N> 66     Breaker failure protection - CBFP 50BF/52BF
  
  • Powerfull motor management
  • 5 time constant accurate thermal model
  • Soft-start protection starting fro 6Hz
  • Star-delta started motor supervision
  • 2-speed motor protection
  • Large customizable HMI with configurable Mimic diagram
  • 16 freely configurable multi-colour LEDs with user description selectable texts
  • Measurement accuracy of up to class 0.2S power and energy measurement
  • 3 Inputs (8/16/24 Optional) - 6 Outputs (5/10/15 Optional)
  • Up to 15000 events in permanent flash memory, 60MB memory for disturbance records and user files
  • IEC 61850, HSR, PRP, IEC 101,IEC 103, IEC 104, Modbus, DNP 3.0, SPA
  • NTP, Precision Time Protocol (PTP) according to IEEE 1588
  • Sub-cycle instantaneous trip times
  • Fast integrated arc protection
  • Frequency independent protection at 6…75Hz

Photos

Videos

Files

Save ×
Save ×

Write To Us

Dear Customer,

We really care about your suggestions.

You can freely post your opinions and complaints if any :) about our company, our products and services.

Our quality department will detailly evaluate your posts and will inform you as soon as possible.

Many thanks for your kind interest.

Best Regards.

RELKO ENERJI


(*)
(*)
(*)
(*)
×

×